Description
Overview:
MOTOMA 5015 ESS is composed of 314Ah battery, liquid-cooling battery pack, battery cluster, power distribution system, liquid-cooling temperature control system, fire protection system, BMS, etc. The rated capacity of the system is 5015.96kWh. Each cluster is equipped with a sub-controller for single-cluster charging and discharging management. Each cluster consists of eight 1P52S battery packs in series. 314Ah high energy density battery cells are used, which is output to the external interface of the container after passing through the sub-controller, and the overall container adopts non-walk-in external maintenance design. It is recommended to be applied to ESS in multiple application scenarios such as peak frequency regulation, output smoothing, power grid support, peak shaving and valley filling in new energy generation side, power grid side and user side.
ESS Parameters:
Type | Name | Parameters | Remarks |
---|---|---|---|
Battery Parameters | Cell type | LFP-3.2V-314Ah | |
Rated capacity [kWh] | 5015.96 | P2, @25°C±3°C | |
Nominal voltage [V] | 1331.2 | ||
Voltage range [V] | 1164.8~1497.6 | ||
Charge and discharge ratio | ≤0.5CP | ||
Max. charging and discharging power [kW] | 2500 | 215kW Modular PCS | |
Operating temperature | Charging: 0~50°C Discharging: -20~55°C | ||
Recommended ambient temperature [°C] | 25±10 | ||
Cycle life | ≥6000 times | 25±10°C, 90%DOD, 80%EOL | |
Cooling method | Liquid cooling | Liquid cooling medium: water + glycol | |
BMS | Level 3 | ||
System Parameters | Auxiliary electrical parameter | ~40kW-400V/50Hz | ~3N+PE |
Fire protection system | Perfluorohexanone + water fire protection | Type S aerosol/HFC-227ea optional | |
Anticorrosive level | C4 | C5 optional | |
Lightning protection level | Level II | ||
Ingress protection | IP55 | ||
Operating temperature range [°C] | -20~+50 | >45°C derating | |
Storage temperature [°C] | -20~+55 | <6 months | |
Operating humidity range | 0~95%RH | No condensation | |
Installation mode | Installation mode | ||
Working condition | Max. 2 charge and 2 discharge per day | ||
System communication interface | CAN/Ethernet/RS485 | ||
External system communication protocol | Modbus TCP | ||
Altitude [m] | ≤3000 | ||
Dimension [W*D*H mm] | 6058*2438*2896 | 20 feet | |
Weight [T] | ~41 | ||
Battery model number | M2500-5015 | ||
Certificate | GB/T 36276, GB/T 34131 |
Main Features:
Safe:
- PACK level + container-level millisecond level sensing to achieve targeted fire extinguishing; gas firefighting.
- water firefighting to prevent re-ignition; active exhaust + third-level explosion venting to prevent secondary damage.
- Three-level thermal insulation for cells, PACK, and clusters, with fire resistance time more than 2 hours.
- PACK, cluster, heap and system four-level fuse protection mechanism, reducing security risks by 30%.
- 5VA-level new flame-retardant insulation material, flame-retardant capability increased by 25%.
Simple:
- 314 AH battery, extremely narrow cold plate, standard 20-foot HQ container nominal energy 5.015MWh, covered area <15m², better EPC cost.
- String architecture, AC side coupling, avoids inter-cluster circulation, and increases available power by 9%.
- The entire container is factory prefabricated, installed, and debugged, and the project delivery time is shortened by 50%.
Intelligent::
- Battery core temperature difference is less than 2.5°C, Al model predicts remaining life and battery core safety risks, guides preventive maintenance, and increases battery life by 12%.
- Active lossless equalization, self-healing and self-balancing, single-cluster automatic switching control, eliminating the need for expert on-site maintenance.
- Intelligent debug detection system to predict error early.